Style Y (Class B) circuits or one Style Z (Class A) circuit.
The zone output(s) from the panel are connected to the
zone inputs of the MDL module and the zone output(s)
from the MDL module are connected to the notification
loop(s). Supervision is accomplished in the module by a di-
rect connection between the zone input and the zone out-
put of each of the two zone circuits connected to the
normal end-of-line device. The FACP "sees" the EOL device
through the MDL module. When either or both outputs
from the module are wired to the SpectrAlert products, the
horns and strobes in both zones will be synchronized.
DC or Full Wave Rectified
11 to 30 Volts
(Note: Supply voltage range at 12 volts – 11 to 17 VDC; at 24 volts – 21 to 30 VDC)
10mA 12mA 30mA 31mA 87mA 122mA
0˚ C to 49˚ C (32˚ F to 120˚ F)
UL S4011, S5512
3825 Ohio Avenue, St. Charles, Illinois 60174
198mA 262mA
The MDL module can be configured so that more than two
zones can be synchronized by the interconnection of the
slave input and output (see Figures 1 and 2).
Zone 1 Input:
This input powers the MDL module. This input
must have voltage present from the FACP be-
fore anything will work. This also supplies volt-
age to Zone 1 output.
Zone 2 Input:
This input only supplies voltage to Zone 2 out-
put. Note: If Zone 1 input is not powered, the
notification devices attached to the Zone 2 out-
put will not be powered.
Horn Control:
This input enables the horns on the SpectrAlert
notification appliances. Voltage present means
horns are enabled. No voltage present means
horns are disabled.
Connects to Master MDL Module slave out.
Connects to Slave MDL slave in.
A Division of Pittway
1-800-SENSOR2, FAX: 630-377-6495
I56-0983-008
Sync module (2 pages)
Sync module (2 pages)
Test module (2 pages)
Monitor module and control module (4 pages)
Ten input monitor module (4 pages)
Interface module (4 pages)
Loop test/maintenance module (2 pages)
Input module for two-wire conventional detector (2 pages)
Two-wire conventional detector interface module (4 pages)
Interface module (2 pages)
Relay control module (2 pages)
Monitor module (2 pages)
Conventional zone interface module (4 pages)
System sensor supervised control module installation and maintenance instructions (4 pages)
Input /output module (4 pages)
Six zone interface module (4 pages)